Type |
Rated Cureent(A) |
Pole number |
Rated Insultating Voltage(V) |
Rated Opreating Voltage(V) |
Ultimate Short circuit breaking capacity(KA) |
Servies short circuit breaking capacity(KA) |
Operation performance (endurance) |
Operation performance |
AC380V (400) |
AC660V (690) |
DC250 |
AC380V (400) |
AC660V (690) |
Load |
Unload |
L |
W(3P/4P) |
H |
AM3-125E |
12.5,16,20, 25,32,40,50, 63,80,100,125 |
Two three four pole |
660V |
≯30 |
15 |
- |
- |
7.5 |
- |
3000 |
7000 |
120 |
76/101 |
70 |
AM3-125S |
25 |
- |
20 |
16 |
- |
AM3-160S |
16,20,32, 40,50,63,80, 100,125,160 |
380V 660V |
35 |
8 |
20 |
18 |
- |
4000 |
6000 |
120 |
90/120 |
70 |
AM3-160H |
50 |
10 |
40 |
25 |
- |
AM3-250S |
100,125, 160,180,200, 225,250 |
35 |
10 |
40 |
18 |
- |
2000 |
6000 |
170 |
105/140 |
103.5 |
AM3-250M |
50 |
16 |
40 |
30 |
- |
AM3-250H |
200,225,250 315,350,400 |
65 |
18 |
40 |
48 |
- |
1000 |
4000 |
254 |
140/184 |
103.5 |
AM3-400S |
35 |
16 |
40 |
18 |
- |
AM3-400M |
50 |
20 |
40 |
20 |
- |
AM3-400H |
65 |
25 |
40 |
48 |
- |
AM3-630S |
400,500,630 |
50 |
20 |
40 |
30 |
- |
1000 |
4000 |
268 |
210/280 |
103.5 |
AM3-630M |
65 |
25 |
40 |
48 |
- |
AM3-630H |
80 |
30 |
40 |
60 |
- |
AM3-800S |
500,630 700,800 |
50 |
20 |
40 |
30 |
- |
1000 |
4000 |
268 |
210/280 |
103.5 |
AM3-800M |
65 |
25 |
40 |
48 |
- |
AM3-800H |
80 |
30 |
40 |
60 |
- |
Motion characteristic |
The thermodynamic release of a circuit breaker provides the feature of inverse time-delay, while the magnetic release is the instantaneous operation as shown on table 2(distribution circuit breaker) and table 3 (motor protection circuit breakers). |
Table 2 |
Rated current of release(A) |
Thermodynamic Release (ambient templand +40℃ marine +45℃) |
Operational current of magnetic release(A) |
1.05In(cold state) inoperative time(h) |
1.30In(heat state) operative time(h) |
10≤In≤63 |
≥1 |
< 1 |
10-50In±20% |
63<In≤250 |
≥2 |
< 2 |
10In±20% 5-10In±20% |
250<In≤800 |
≥2 |
< 2 | |
|
Table 3 |
Rated current of release(A) |
Thermodynamic Release (ambient templand +40℃ marine +45℃) |
Operational current of magnetic release(A) |
1.0In(cold state) inoperative time(h) |
1.20In(heat state) operative time(h) |
1.50In(heat state) operative time(h) |
7.2In(cold state) operative time(h) |
12.5≤In≤400 |
2 |
2 |
4min |
2s<Tp≤10s |
12In±20% | | | | |