Contactor type |
CJX1-9 CJX1-12 |
CJX1-16 CJX1-22 |
CJX1-32 |
CJX1-45 CJX1-63 |
CJX1-75 CJX1-85 |
CJX1-110 CJX1-140 |
CJX1-170 CJX1-205 |
CJX1-250 CJX1-300 |
CJX1-400 CJX1-475 |
Machinical endurance(X 106) |
10 |
10 |
10 |
10 |
10 |
6 |
8 |
8 |
8 |
Conventional thermal current |
20 |
30 |
45 |
80 |
100 |
160 |
200/200 |
300 |
400/500 |
Rated Insulation voltage |
660 |
660 |
660 |
1000 |
1000 |
1000 |
1000 |
1000 |
1000 |
Rated insulation current(A) |
380V |
9/12 |
16/22 |
32 |
45/63 |
75/85 |
110/140 |
170/205 |
250/300 |
400/475 |
660V |
7.2/9.5 |
13.5 |
18 |
45/63 |
75/85 |
110/140 |
170/205 |
250 |
400 |
Power of controllable motor(KW) |
380V |
4/5.5 |
7.5/11 |
15 |
22/30 |
37/45 |
55/75 |
90/110 |
132/160 |
200/250 |
660V |
5.5/7.5 |
11 |
15 |
39/55 |
67 |
100 |
156 |
235 |
375 |
Powr of controllable motor(KW) |
380V |
1.4/1.9 |
3.5/4 |
7.5 |
12/14 |
17/21 |
27/35 |
38/50 |
58/66 |
81 |
660V |
2.4/3.3 |
6/6.6 |
11 |
20.8/24 |
29.5/36 |
46.9/60 |
66/86 |
100/114 |
140 |
Frequency of operation(1/h) |
AC3 |
1200 |
600 |
600 |
1200/1000 |
1000 |
1000 |
700/500 |
700/500 |
500/420 |
AC4 |
300 |
300 |
300 |
600/400 |
400 |
400 |
300/130 |
200/130 |
150 |
Electrical endurance(X 106) |
AC3 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0/0.8 |
0.8 |
0.8 |
AC4 |
0.2 |
0.2 |
0.2 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
0.1 |
Operating voltage range of coll |
(0.8~1.1)Ue |
Power consumption of coll |
Atracting(VA) |
10 |
10 |
10 |
17 |
32 |
39 |
58 |
84 |
115 |
Starting(VA) |
68 |
69 |
71 |
183 |
330 |
550 |
910 |
1430 |
2450 |
Rated insulation voltage of auxitiary contacts (V) |
660 |
660 |
660 |
660 |
660 |
660 |
660 |
660 |
660 |
Conventional thermal current of auxitiary contacts(A) |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Rated operating current of auxitiary contacts (A) |
Ac15 380/660 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
1.9/1.1 |
Dc13 220V |
0.15 |
0.15 |
0.15 |
0.15 |
0.15 |
0.15 |
0.15 |
0.15 |
0.15 |