APPLICATION
KEY FEATURES
TECHNICAL SPECIFICATIONS
Model |
G6KN | G10KN | |
Rated Power |
VA/W | 6kVA/4.2kW | 10kVA/7kW |
Input |
Nominal Voltage | 220VAC | |
VoltageRange | 176 ~ 276VAC | ||
FrequencyRange | 46 ~ 54Hz | ||
Power Factor | 0.98 | ||
Connection | Hardwired | ||
Output |
Voltage | 220VAC ±1% | |
Frequency | 50Hz ±0.1% (Battery mode) | ||
Waveform | Sine Wave | ||
Power factor | 0.7 | ||
Voltage Distortion | 2% under linear load | ||
Overload Capability | 105% ~ 130% for 10 min., ³130% for 1 min. | ||
Current Crest Ratio | 3:1 max. | ||
Connection | Hardwired | ||
Battery |
Type | Sealed, Maintenance free, Lead-Acid (Panasonic) | |
Quantity | 20 pieces | ||
Back-up time (full load) | 7 min | 5 min | |
Recharge time | 8 hrs to 90% of capacity after full load discharge | ||
Transfer time |
0 ms | ||
Maintenance Bypass Switch |
Yes | ||
LED indicators |
Status | Load level/Battery level,Battery , Utility power, Inverter, Bypass, Overload, Fault | |
Audible alarm |
Bypass | Alarm beeps every two minutes | |
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||
Overload | Alarm beeps two for every second | ||
Fault | Alarm beeps continuously | ||
Acoustic noise |
At 1 meter distance | £ 55 dBA | |
Communications |
DB-9 Port | RS232 serial interface | |
Intelligent Slot | Options: WebPower, AS400 or WinPower CMC | ||
ParallelPort |
up to three units in parallel for power redundancy and load sharing | ||
Environmental |
Operating temperature | 0 ~ 40°C | |
Operating humidity | 20% ~ 90% non-condensing | ||
Weight |
Net (kg) | 84 | 93 |
Dimensions |
W x D x H (mm) | 260 x 570 x 717 |
Model |
G6KNS | G10KNS | |
Rated Power |
Volt-Amps/Watts (VA/W) | 6kVA/4.2kW | 10kVA/7kW |
Input |
Nominal Voltage | 220VAC | |
VoltageRange | 176 ~ 276VAC | ||
FrequencyRange | 46 ~ 54Hz | ||
Power Factor | 0.98 | ||
Connection | Hardwired | ||
Output |
Voltage | 220VAC ±1% | |
Frequency | 50Hz ±0.1% (Battery mode) | ||
Waveform | Sine Wave | ||
Power factor | 0.7 | ||
Voltage Distortion | 2% under linear load | ||
Overload Capability | 105% ~ 130% for 10 min., ³130% for 1 min. | ||
Current Crest Ratio | 3:1 max. | ||
Connection | Hardwired | ||
Battery |
Type | Sealed, Maintenance free, Lead-Acid (Panasonic) | |
Nominal DC Voltage | 240VDC | ||
Back-up time | Depends on the capacity of the external battery bank | ||
Connection | ExternalBattery Socket | ||
Transfer time |
0 ms | ||
Maintenance Bypass Switch |
Yes | ||
LED indicators |
Status | Load level/Battery level,Battery , Utility power, Inverter, Bypass, Overload, Fault | |
Audible alarm |
Bypass | Alarm beeps every two minutes | |
Battery discharge | Alarm beeps every four seconds, every second if battery low | ||
Overload | Alarm beeps two for every second | ||
Fault | Alarm beeps continuously | ||
Acoustic noise |
At 1 meter distance | £ 55 dBA | |
Communications |
DB-9 Port | RS232 serial interface | |
Intelligent Slot | Options: WebPower, AS400 or WinPower CMC | ||
ParallelPort |
up to three units in parallel for power redundancy and load sharing | ||
Environmental |
Operating temperature | 0 ~ 40°C | |
Operating humidity | 20% ~ 90% non-condensing | ||
Weight |
Net (kg) | 35 | 38 |
Dimensions |
W x D x H (mm) | 260 x 570 x 717 |